Total Power Solutions
Our catalogues

Our catalogues

German    English    French
Alpha Cell

Alpha Cell

GelCell Batteries

Alpha Cell
Data sheet
Downloads
Source of supply

Alpha’s standby battery offering incorporates Gel for thermal dissipation to ensure optimal life performance for your particular Broadband application. The AlphaCell batteries provide the longest runtimes and the best longevity in today’s demanding outdoor non-temperature controlled cable power environments. All backed with industry leading full non-prorated warranties.

GXL and GXL-HP:

  • High-performance Silver Alloy for maximum life expectancy
  • Increased runtime for VoIP networks
  • 100% runtime capacity out-of-box – No cycling required
  • Maintenance-free threaded inserts — no periodic retorquing

Variants Technical data

 

General Specifications
Model: 220 GXL
195 GXL
85 GXL-HP
Warranty: 5 to 6 years 5 to 6 years 5 years
Service Life: Extended Extended Extended
Runtime (minutes)2: 221 196 85
VRLA Batterie Type: Gel Silver Alloy Gel Silver Alloy Valve Regulated Lead Acid
Heat Resistant: Extreme Extreme Extreme
Hydrogen Emission: Low Low Low
Terminals:

Threaded insert 1/4” - 20 UNC

Threaded insert 1/4” - 20 UNC

Threaded insert 10 - 32 UNF

Cells Per Unit: 6 6 6
Voltage Per Unit: 12.8 12.8 12.8
Conductance Value: 1175 1100 600
Max. Discharge Current (A): 900 900 600
Short Circuit Current (A): 2800 2600 2200
10 Second Volts @ 100A: 11.4 11.3 10.8
Ohms Impedance 60Hz: 0.0050 0.0050 0.0065
Capacity at 20hrs: (to 1.75VPC) 109Ah 100Ah 50Ah
BCI Group Size: 31 31 22
Weight (lb/kg): 73/33.2 67/30.5 39.6/18
Height w/ Terminals (in/mm): 8.5/215 8.5/215 8.1/206
Width (in/mm)3: 13.4/341 13.4/341 9/228
Depth (in/mm)3: 6.80/173 6.80/173 5.5/139
Operating Temperature Range
Discharge:
-40 to 71°C (-40 to 160°F)
Charge (with temp compensation): -23 to 60°C (-9.4 to 140°F)
Float Charging Voltage (VDC): 13.5 to 13.8 13.5 to 13.8 13.5 to 13.8
AC Ripple Charger: 0.5% RMS or 1.5% of float charge voltage recommended for best results. Max. allowed = 4% pk to pk

Notes:
1 Warranty varies by country and region. Warranty valid only when used with Alpha approved Power Supplies, Chargers and Enclosures. Consult your sales person for details.
2 Runtimes calculated using a 25A DC constant current load with voltage discharge to 1.75V/cell @ 25°C.
3 Dimensions at top of battery.
4 In Canada, the Gold warranty is 6 years when AlphaGuardTM Charge Management is used in the battery string, and 5 years if AlphaGuard Charge Management is not used.