| Model: |
GMX 915 |
GMX 915P |
GMX 915E |
| Electrical |
| Input Voltage: |
115Vrms |
225Vrms |
225Vrms |
|
Input Tolerance:
|
Operating: ±30% (80 to 150Vrms) Line Return: ±25% |
Operating: ±30% (158 to 292Vrms) Line Return: ±25% |
Operating: ±30% (158 to 292Vrms) Line Return: ±25% |
|
Nominal Input Current1:
|
13A |
7A |
7A |
| Input Frequency (without going to standby): |
60Hz, ±3Hz |
60Hz, ±3Hz |
50Hz, ±3Hz |
| DC Voltage: |
36VDC |
36VDC |
36VDC |
| Low DC Voltage Cutout: |
1.75V/Cell |
1.75V/Cell |
1.75V/Cell |
| Output Voltage: |
63/87Vrms (Field Selectable) |
63/87Vrms (Field Selectable) |
63/87Vrms (Field Selectable) |
| Output Regulation, 87V Tap2: |
±3% |
±3% |
±3% |
| Output Regulation, 63V Tap2: |
±4% |
±4% |
±4% |
| Rated Output Current: |
15A rms |
15A rms |
15A rms |
| Output Configuration: |
Single |
Single |
Single |
| Output Frequency: |
60Hz, ±1Hz (Inverter Operation) |
60Hz, ±1Hz (Inverter Operation) |
50Hz, ±1Hz (Inverter Operation)Quasi Square wave |
| Waveform: |
Quasi Square wave |
Quasi Square wave |
|
| Slew Rate: |
<200 V/ms,<100 V/ms typical |
<200 V/ms,<100 V/ms typical |
<200 V/ms,<100 V/ms typical |
| Crest Factor Ratio (Peak: RMS): |
1.3:1 typical |
1.3:1 typical |
1.3:1 typical |
| Efficiency @ 87Vrms |
| @100% Load: |
91% typical at nominal input |
91% typical at nominal input |
91% typical at nominal input |
| @75% Load: |
90% typical at nominal input |
90% typical at nominal input |
90% typical at nominal input |
| @50% Load: |
88% typical at nominal input |
88% typical at nominal input |
88% typical at nominal input |
| @25% Load: |
80% typical at nominal input |
80% typical at nominal input |
80% typical at nominal input |
| On Inverter (40 to 100% load): |
84% typical |
84% typical |
84% typical |
| Overload Protection |
| Fold back (Typical @ Nominal Input) |
|
|
|
| 87V Tap: |
24A rms |
24A rms |
24A rms |
| 60V Tap: |
33A rms |
33A rms |
33A rms |
| Output Current Into Short (@ Nominal Input) |
|
|
|
| 87V Tap: |
<22.5A rms |
<22.5A rms |
<22.5A rms |
| 60V Tap: |
29A rms typical |
29A rms typical |
29A rms typical |
| Overload Current Operation |
|
|
|
| 0% to 110% Load: |
Continuous Operation |
Continuous Operation |
Continuous Operation |
| 115 to 125% Load: |
Shut Down approx. 30min |
Shut Down approx. 30min |
Shut Down approx. 30min |
| 125 to 150% Load: |
Shut Down approx. 10min |
Shut Down approx. 10min |
Shut Down approx. 10min |
| >150% Load: |
Shut Down <10sec |
Shut Down <10sec |
Shut Down <10sec |
| Battery Charging |
| Charge Current: |
10A4 |
10A4 |
10A4 |
| Temperature Compensation: |
-5mV/Cell/°C (Programmable) |
-5mV/Cell/°C (Programmable) |
-5mV/Cell/°C (Programmable) |
| Constant Current Operation: |
High Rate Charge to 90% Capacity |
High Rate Charge to 90% Capacity |
High Rate Charge to 90% Capacity |
| Constant Voltage Operation: |
2.40V/Cell (Typ. 7hrs) |
2.40V/Cell (Typ. 7hrs) |
2.40V/Cell (Typ. 7hrs) |
| Environmental |
| Operating Range: |
–40 to 55°C at Front Air Inlet of Power Supply |
–40 to 55°C at Front Air Inlet of Power Supply |
–40 to 55°C at Front Air Inlet of Power Supply |
| Humidity: |
0 to 95% non-condensing |
0 to 95% non-condensing |
0 to 95% non-condensing |
| Altitude: |
0 to 10000ft (3000m) above sea level |
0 to 10000ft (3000m) above sea level |
0 to 10000ft (3000m) above sea level |
| Mechanical |
|
Height
(in):
(mm):
|
7.8
198 |
7.8
198 |
7.8
198 |
Width
(in):
(mm): |
18.3
465 |
18.3
465 |
18.3
465 |
Depth
(in):
(mm): |
11.4
290 |
11.4
290 |
11.4
290 |
Weight
(lb):
(kg): |
60
27.5
|
60
27.5 |
67
30.5 |
| Front Panel Display (LCD): |
2 x 20 Character LCD |
2 x 20 Character LCD |
2 x 20 Character LCD |
| Front Panel Indicators (LED): |
Output Status & Alarm |
Output Status & Alarm |
Output Status & Alarm |
| Finish: |
Black Powder Coat |
Black Powder Coat |
Black Powder Coat |
| Communication |
| Status Monitoring3: |
Optional |
Optional |
Optional |
| Agency |
| Safety Recognition: |
UL 1778/CSA C22.2, No. 107.1 |
UL 1778/CSA C22.2, No. 107.1 CB scheme CE and KTL |
EN 50091-1-2, IEC 60950 CCC, |
| Emissions: |
CISPR 22, Class A |
CISPR 22, Class A |
EN 50091-2, (CE Class A) |