Total Power Solutions
Our catalogues

Our catalogues

German    English    French
TRI-Power X33 SCR

TRI-Power X33 SCR

3phase UPS 10 to 300kVA

TRI-Power X33 SCR
Data up to 40kVA
Data up to 160kVA
Data up to 300kVA
Downloads
Source of supply

Standard features are galvanic isolation transformers at the inverter input providing highest protection against all kind of power disturbances also the possibility of 100% non-linear driving capability and dry contacts. Due to the technology this UPS can be installed in almost every ambient condition with an extreme reliability and a high MTBF value. The Tri Power X33 SCR can be used for any kind of load i.e. IT, Industry and Telecom.

Model range available: 10 to 300kVA

  • Galvanic isolation transformer at the inverter output
  • Non-linear load driving capability
  • RS232 and dry contacts
  • Overload and short circuit protection
  • Emergency stop utility

 

Variants Technical data

Technical Data
Model X33 SCR 10 X33 SCR 15 X33 SCR 20 X33 SCR 30 X33 SCR 40
Power (kVA) 10 15 20 30 40
INPUT
Voltage 230/400 VAC 3phase +N; ±15%
By-pass Voltage 230/400 VAC 3phase +N; ±10% (lower and upper limit are adjustable)
Input frequency 50 Hz (60Hz on request), ±5%
Max RFI EN 50091-2 Class A
OUTPUT
Power (kW) 8 12 16 24 32
Power factor 0.8
Voltage 230/400 VAC 3phase +N
Voltage Stability (balanced load: ± 1%) (unbalanced load: ± 2%) (step load: ± 5%)
Voltage recovery time after step load: within 35ms
Frequency 50 Hz (60 Hz)
Frequency tolerance (line synchronized: ± 1%) (free running: ± 0.2%)
Efficiency at 100% load 90 - 92% 91 - 93%
Crest factor 3 : 1
Overload protection (100%-125% load: 10min) (125%-150% load: 1min) (>150% load: by pass)
Short circuit protection Electronic short circuit protection
Total harmonic distortion linear load: <3% ; non linear load: <5%
BATTERIES
Type Sealed Lead Acid - Maintenance Free
Number of Batteries 30
Float charging voltage 405 VDC
End of discharge voltage 300 VDC
Ambient temperature °C 25 °C
Battery protection Wall mounted circuit breaker and fuse
Battery test Automatic and manual
GENERAL
Serial communication Dry contacts & RS232; RS485
Software T-Mon UPS Management Software
Temperature range 0°C - 40°C
Ventilation Forced air cooling
Relative humidty < 90% non condensing
Protection degree IP 20
Altitude < 1000m above sea level
Accoustic noise < 56dBA
Weight w/o batteries (kg) 235 250 266 322 484
Dimensions HxWxD (mm): 1145x485x675 1400x570x820
OPTIONS
Input transformer Galvanic isolation transformer at the input (in external cabinet)
Input THD < 10% with 12 pulse or 18 pulse rectifier; < 5% with 18 pulse rectifier + filter (up to 80kVA)
Parallel operation N +1 systems (hot standby, redundant, symetric parallel)

 

Model X33 SCR 60 X33 SCR 80 X33 SCR 100 X33 SCR 120 X33 SCR 160
Power (kVA) 60 80 100 120 160
INPUT
Voltage 230/400 VAC 3phase +N; ±15%
By-pass Voltage 230/400 VAC 3phase +N; ±10% (lower and upper limit are adjustable)
Input frequency 50 Hz (60Hz on request), ±5%
Max RFI EN 50091-2 Class A
OUTPUT
Power (kW) 48 64 80 96 128
Power factor 0.8
Voltage 230/400 VAC 3phase +N
Voltage Stability (balanced load: ± 1%) (unbalanced load: ± 2%) (step load: ± 5%)
Voltage recovery time after step load: within 35ms
Frequency 50 Hz (60 Hz)
Frequency tolerance (line synchronized: ± 1%) (free running: ± 0.2%)
Efficiency at 100% load 90 - 92% 91 - 93%
Crest factor 3 : 1
Overload protection (100%-125% load: 10min) (125%-150% load: 1min) (>150% load: by pass)
Short circuit protection Electronic short circuit protection
Total harmonic distortion linear load: <3% ; non linear load: <5%
BATTERIES
Type Sealed Lead Acid - Maintenance Free
Number of Batteries 30
Float charging voltage 405 VDC
End of discharge voltage 300 VDC
Ambient temperature °C 25 °C
Battery protection Wall mounted circuit breaker and fuse
Battery test Automatic and manual
GENERAL
Serial communication Dry contacts & RS232; RS485
Software T-Mon UPS Management Software
Temperature range 0°C - 40°C
Ventilation Forced air cooling
Relative humidty < 90% non condensing
Protection degree IP 20
Altitude < 1000m above sea level
Accoustic noise 60dBA 65dBA
Weight w/o batteries (kg) 562 620 770 810 960
Dimensions HxWxD (mm): 1145x485x675 1400x710x800 1650x1100x800 1730x1195x870
OPTIONS
Input transformer Galvanic isolation transformer at the input (in external cabinet)
Input THD < 10% with 12 pulse or 18 pulse rectifier; < 5% with 18 pulse rectifier + filter (up to 80kVA)
Parallel operation N +1 systems (hot standby, redundant, symetric parallel)

 

Model X33 SCR 200 X33 SCR 250 X33 SCR 300
Power (kVA) 200 250 300
INPUT
Voltage 230/400 VAC 3phase +N; ±15%
By-pass Voltage 230/400 VAC 3phase +N; ±10% (lower and upper limit are adjustable)
Input frequency 50 Hz (60Hz on request), ±5%
Max RFI EN 50091-2 Class A
OUTPUT
Power (kW) 160 200 240
Power factor 0.8
Voltage 230/400 VAC 3phase +N
Voltage Stability (balanced load: ± 1%) (unbalanced load: ± 2%) (step load: ± 5%)
Voltage recovery time after step load: within 35ms
Frequency 50 Hz (60 Hz on request)
Frequency tolerance (line synchronized: ± 1%) (free running: ± 0.2%)
Efficiency at 100% load up to 93%
Crest factor 3 : 1
Overload protection (100%-125% load: 10min) (125%-150% load: 1min) (>150% load: by pass)
Short circuit protection Electronic short circuit protection
Total harmonic distortion linear load: <3%; non linear load: <5%
BATTERIES
Type Sealed Lead Acid - Maintenance Free
Number of Batteries 30 32
Float charging voltage 405 VDC 432 VDC
End of discharge voltage 300 VDC 320 VDC
Ambient temperature °C 25 °C
Battery protection wall mounted circuit breaker and fuse
Batterietest automatic and manual
GENERAL
Serial communication Dry contacts & RS232; RS485
Software T-Mon UPS Management Software
Temperature range 0°C - 40°C
Ventilation Forced air cooling
Relative humidty < 90% non condensing
Protection degree IP 20
Altitude < 1000m über NN
Accoustic noise 70dBA
Weight w/o batteries (kg) 1150 1285 1416
Dimensions HxWxD (mm) 1730x1195x870 1880x1565x925
OPTIONS
Input transformer Galavanic isolation transformer at the input
Input THD < 10% with 12 pulse or 18 pulse rectifier; < 5% with 18 pulse rectifier + filter (up to 80kVA)
Parallel operation N +1 systems (hot standby, redundant, symetric parallel)