| Input |
| Voltage Range: |
90 to 132, or 180 to 264Vac (switch selectable) or 220 to 305Vac or 280 to 382Vac with optional step-down transformers |
| Frequency: |
47 to 63Hz |
| Surge Protection: |
ANSI/IEEE Std. C62.41 to Category A, B, or C requirements, using a “Ring Wave” or “Combination” waveform, at a level of 6kV |
| Output |
| Voltage: |
42 to 56Vdc |
| Power: |
50W continuous |
| Ripple: |
<250mVrms |
| Noise: |
<2Vp-p |
| Transfer Characteristics: |
Uninterrupted upon loss of AC service |
| Battery |
| Type: |
Four valve-regulated lead-acid (VRLA) (Batteries sold separately) |
| Storage Temperature: |
-4° to 104°F/-20° to 40°C |
| Capacity: |
7.2Ah @ 20 hr. rate to 1.75Vdc |
| Dimensions with terminal (in/mm): |
5.94L x 2.56W x 3.86H/151L x 65W x 98H |
| Dimensions without terminal (in/mm): |
5.94L x 2.56W x 3.70H/151L x 65W x 94H |
| Weight (lb/kg): |
5.95/2.7 |
| Runtime @ 77°F/25°C: |
18 hrs. 20W load, 8 hrs. 40W load |
| Recharge @ 77°F/25°C: |
13 hrs. 20W load, 25 hrs. 40W load |
| Alarms |
| MPS48-7T: |
Dry contact, Visual with LED's |
| MPS48-7F: |
Visual with LED's and electrically per PacketCableTM UPS |
| LED Status Indicators |
| Green Steady: |
Output within parameters |
| Green Blinking: |
Standby Operation |
| Red Blinking: |
Low or Missing Battery |
| Red Steady: |
Replace Battery |
| Remote – Five 24 gauge wires from UPS to ONT |
| AC Fail |
Output power drawn from battery |
| Replace Battery |
Battery has failed periodic self test |
| Battery Missing |
Battery is disconnected |
| Battery Low |
Indicates battery has <40% remaining runtime |
| AC Fail |
loss of service AC alarm |
| Options |
Battery heater mats
Batteries
277Vac step down transformer
347Vac step down transformer
Street light power tap
Power cord |
| Mechanical |
| Unit |
|
| Dimensions (in/mm): |
17.5H x 12.75W x 5.25D/445H x 324W x 133D |
| Weight (lb/kg): |
11/4.9 (not including battery) |
| ELH100 Apollo (lb/kg): |
11.234/5.096 |
ELH100 Apollo (with wall
mount brackets) (lb/kg): |
15.64/7.094 |
| |
|
| Unit and carton |
|
| Dimensions (in/mm): |
19.9H x 16W x 7.25D/505H x 406W x 184D |
| Weight (lb/kg): |
11/4.9 (not including battery) |
| Weight (lb/kg): |
34.6/15.7 (including battery) |
| |
|
| Operating Temperature |
|
| With Heater Option: |
-40° to 131°F/-40° to 55°C |
| Without Heater Option: |
-4° to 131°F/-20° to 55°C |
| Storage Temperature: |
-58° to 158°F/-50° to 70°C |
| Humidity: |
0 to 95% |
| Altitude: |
Up to 10,000 ft./3,000m with ambient derating Above 6,000 ft./1,800m, 36°F/2°C per 1,000 ft./300m |
| Regulatory |
Agency Compliance
FCC/GR1089 Class B, CSA-NRTL\C (CSA60950), CE, C-Tic,
RoHS compliant per European Union’s Directive
2002/95/EC, Restrictions of Hazardous Substances
Siesmic Zone 4 rated per GR-63
Complies with IPx5 water intrusion criteria per IEC
60529 standard |