The TRI-POWER X33 is a high performance 10-800kVA UPS system with redundant processor controlling. The integrated intelligent Energie Management provides optimised efficiency operation. The TRI-POWER X33 protects all loads and is up to 99% efficient. This UPS is specially designed for telecom, industry and fire protecting applications.

  • Online, VFI-SS-111
  • Static and maintenance bypass
  • THDI up to 5%
  • Efficiency up to 99%
  • LCD panel with back lighting
  • Interface card
  • Up to 8 systems in parallel

Technical data

Specifikation
Size in kVA at cos phi = 0,8 20 30 40 60 80

Rectifier
 
Nominal Input Voltage (V): 400V three phase (380V, 415V on request), 50/60Hz selectable
Nominal Input Voltage (V): +15 /-15 +15 /-15 +15 /-15 +15 /-15 +15 /-15
Tolerance of voltage (without battery charge) (%): -25 -25 -25 -25 -25
Frequency range (Hz): 45–65 45–65 45–65 45–65 45–65
THD at input, incl. Filter + 12pulse rectifier (Option) (%):
≤5

≤5

≤5

≤5

≤5
Medium power factor, including THD-filter (cos phi):
≥0,96

 
≥0,96


≥0,96

≥0,96

≥0,96
Softstart adjustable (in sec.): 0,10,20,30
Battery charging current min. (A): 2 2 2 5 5
Battery charging current max. (A): 46 64 91 126 171

Battery
         
Recommended power of battery needed, total (kW):
16.9

25.3

 
33.6


50.4

67.2
Power of battery in watt per each cell (W) (1 line): 85.6 127.9 169.9 254.4 339.2
Recommended nos. of Pb cells: 198.0 198.0 198.0 198.0 198.0
End of discharge voltage (V): 316.8 316.8 316.8 384.0 384.0

Inverter
         
Nominal power at P. F. 0,8 inductive: 20 30 40 60 80
Nominal power at P. F. 1,0 (kW): 16 24 32 48 64
Nominal output current at 400VAC and 0,8 P. F. (A):
29


44


58

87

116
Nominal voltage (V): 400V three phase (380V, 415V on request) + Neutral 50/60Hz
Crest factor at 100% balanced load: 5 5 5 5 5
Inverter efficiency at full nominal load (%): 94.4% 94.8% 95.1% 95.3% 95.3%
Overload at 400VAC, 0.8 P. F. 150% Pn x 20 (min):
20

20

20

20

20
Overload at 400VAC, 0.8 P. F. 125% Pn x 90 (sec.):
90

90

90

90

90
3 ph. Short circuit current 5 sec. (%) 180 180 180 180 180
1 ph. Short circuit current 5 sec. (%) 220 220 220

 220

220

Reserve line (static switch):
 
Nominal input voltage (V): 400V three phase (380V, 415V on request) + Neutral 50/60Hz
Nominal frequency (Hz): 45–65 45–65 45–65 45–65 45–65

Internal manual bypass (service bypass):

Standard integrated

General System Data
 
Radio interference suppression and immunity, acc. To:


EN 50091-2

Operating mode: Online, double conversion, acc. to VFI-SS-111 class A

Efficiency, high efficiency plus mode (%):

99.2

99.2

99.2

99.3

99.3
Efficiency, high efficiency quality mode (%): 97.1 97.1 97.1 97.1 97.3
Efficiency, acc. to VFI-SS-111 (opt. load) (%): 92.2 92.4 92.1 92.2 92.9

Norms, acc. to:
 

EN 50091 - 1 - 2 - 3 ; IEC 62040 - 1 - 2 - 3; VDE 0558, VFI-SS-111 Klasse A
MTBF (mean time between failure): 20.000Hrs
Parallel mode, n+1 systems, up to: 8 8 8 8 8
Cabinet type: Industry steel cabinet, RAL 7035
Cooling: Self cooling, redundancy fans

Dimensions + Weights (standard)
         
Height (mm): 1200 1200 1200 1400 1400
Width (mm): 555 555 555 800 800
Depth (mm): 720 720 720 740 740
Weight UPS (kg): 230 282 330 450 550
Footprint (m2): 0.47 0.47 0.47 0.47 0.60
Load capacity (kg/m2): 535 588 642 791 914

Interfaces
 
  1. Serial RS 232, Sub-D 9pin, standard protocol, Male
2. Serial RS 232, Sub-D 9pin, J-BUS, Male
3. Serial RS 232, Sub-D 9pin, MOD-BUS, Male
4. Serial RS 232, Sub-D 9pin, PROFIBUS-Connector, Male
5. IBM AS400, Sub-D 9pin, Female
6. Potential free Relays, 10 + 5 Indications, programmable
7. GenSet operation, stop battery charging, input
8. GenSet operation, synchronising free running
9. EPO emergency power off, potential free input
9. EPO emergency power off, potential free output
11. Fibre optic for remote control (potential free) TX
12. Fibre optic up to 8-systems parallel (pot. free) RX/TX
13. SNMP-connector RS232, Sub-D 9pin for SNMP-Module

Specifikation
Size in kVA at cos phi = 0,8 100 120 160 200 250 300 400 600
Rectifier
Nominal Input Voltage (V):

400V three phase (380V, 415V on request), 50/60Hz selectable
Nominal Input Voltage (V): +15 /-15 +15 /-15 +15 /-15 +15 /-15 +15 /-15 +15 /-15 +15 /-15 +15 /-15
Tolerance of voltage (without battery charge) (%):
-25

-25

-25

-25

-25

-25

-25

-25
Frequency range (Hz): 45–65 45–65 45–65 45–65 45–65 45–65 45–65 45–65
THD at input, incl. Filter + 12pulse rectifier (Option) (%):
≤5

≤5

≤5

≤5

≤5

≤5

≤5

≤5
Medium power factor, including THD-filter (cos phi):
≥0,96

 
≥0,96


≥0,96

≥0,96

≥0,96

≥0,96

≥0,96

≥0,96
Softstart adjustable (in sec.): 0,10,20,30
Battery charging current min. (A): 5 5 5 5 10 10 10 30
Battery charging current max. (A): 216 252 342 414 522 536 860 1055

Battery
Recommended power of battery needed, total (kW):



83.9



100.7

 


134.3




167.9



210.5



252.1



333.3



495.9
Power of battery in watt per each cell (W) (1 line):
424.0

508.8

678.3

847.9

1063.3

1050.4

1388.9

2066.1
Recommended nos. of Pb cells: 198.0 198.0 198.0 198.0 198.0 240.0 240.0

240.0

End of discharge voltage (V): 316.8 316.8 316.8 384.0 384.0 384.0 384.0 384.0

Inverter
Nominal power at P. F. 0,8 inductive:


100


120


160


200


250


300


400


600
Nominal power at P. F. 1,0 (kW): 80 96 128 160 200 240 320 480
Nominal output current at 400VAC and 0,8 P. F. (A):
145


174


231

289

361

434

578

867
Nominal voltage (V): 400V three phase (380V, 415V on request) + Neutral 50/60Hz
Crest factor at 100% balanced load: 5 5 5 5 5 5 5 5
Inverter efficiency at full nominal load (%):
95.3%

95.3%

95.3%

95.3%

95.0%

95.2%

96.0%

96.8%
Overload at 400VAC, 0.8 P. F. 150% Pn x 20 (min):
20

20

20

20

20

20

20

20
Overload at 400VAC, 0.8 P. F. 125% Pn x 90 (sec.):
90

90

90

90

90

90

90

90
3 ph. Short circuit current 5 sec. (%) 180 180 180 180 180 180 180 180
1 ph. Short circuit current 5 sec. (%) 220 220 220

 220

220 220 220 220

Reserve line (static switch):
Nominal input voltage (V):


400V three phase (380V, 415V on request) + Neutral 50/60Hz
Nominal frequency (Hz): 45–65 45–65 45–65 45–65 45–65 45–65 45–65 45–65

Internal manual bypass (service bypass):


Standard integrated

General System Data
Radio interference suppression and immunity, acc. To:




EN 50091-2

Operating mode: Online, double conversion, acc. to VFI-SS-111 class A

Efficiency, high efficiency plus mode (%):


99.3


99.3


99.3


99.3


99.2


99.2


99.2


99.3
Efficiency, high efficiency quality mode (%):
97.3

97.3

97.5

97.5

97.5

97.5

97.5

97.5
Efficiency, acc. to VFI-SS-111 (opt. load) (%):
93.8

93.6

94.4

94.7

93.8

94.03

94.5

94.9

Norms, acc. to:
 

EN 50091 - 1 - 2 - 3 ; IEC 62040 - 1 - 2 - 3; VDE 0558, VFI-SS-111 Klasse A
MTBF (mean time between failure): 20.000Hrs
Parallel mode, n+1 systems, up to: 8 8 8 8 8 8 8 8
Cabinet type: Industry steel cabinet, RAL 7035
Cooling: Self cooling, redundancy fans

Dimensions + Weights (standard)
Height (mm):


1900


1900


1900


1900


1950



1900



1900


1900
Width (mm): 800 800 800 800 1100 1630 1630 3200
Depth (mm): 800 800 800 800 800 800 1000 1000
Weight UPS (kg): 640 650 770 810 1650 2200 2600 4000
Footprint (m2): 0.88 0.88 0.88 1.50 2.70 2.70 2.70 2.70
Load capacity (kg/m2): 1045 1591 1875 1200 1074 1148 1444 1778

Interfaces
 
  1. Serial RS 232, Sub-D 9pin, standard protocol, Male
2. Serial RS 232, Sub-D 9pin, J-BUS, Male
3. Serial RS 232, Sub-D 9pin, MOD-BUS, Male
4. Serial RS 232, Sub-D 9pin, PROFIBUS-Connector, Male
5. IBM AS400, Sub-D 9pin, Female
6. Potential free Relays, 10 + 5 Indications, programmable
7. GenSet operation, stop battery charging, input
8. GenSet operation, synchronising free running
9. EPO emergency power off, potential free input
9. EPO emergency power off, potential free output
11. Fibre optic for remote control (potential free) TX
12. Fibre optic up to 8-systems parallel (pot. free) RX/TX
13. SNMP-connector RS232, Sub-D 9pin for SNMP-Module