Total Power Solutions
Our catalogues

Our catalogues

German    English    French
TRI-Power X31 SCR

TRI-Power X31 SCR

TRI-Power X31 SCR
data sheet
Downloads
Source of supply

Standard features are galvanic isolation transformers at the inverter input providing highest protection against all kind of power disturbances also the possibility of using dry contacts. Due to the technology this UPS can be installed in almost every ambient condition with an extreme reliability and a high MTBF value. The Tri Power X31 SCR can be used for any kind of load i.e. IT, Industry and Telecom.

  • Models: 6 to 30kVA
  • Single phase output
  • Galvanic isolation transformer at the inverter output
  • RS232 and dry contacts
  • Overload and short circuit protection
  • Emergency stop utility

Variants Technical data

 

Technical Data
Model X31 SCR
 6 7.5 10 15 20 30
Power (kVA) 6 7.5 10 15 20 30 
INPUT
Voltage 230/400 VAC 3phase +N; ±15%
By-pass Voltage 220 or 230 VAC ±10% (lower and upper limit are adustjable)
Current 3x12A 3x15A 3x20A 3x30A 3x40A 3x60A  
Input Frequenzy 50 Hz (60Hz on request), ±5%
EMV EN 50091-2 Class A
OUTPUT
Power (kW) 4.2 5.25 7 10.5 14 21 
Power factor 0.7
Voltage 220 or 230 VAC ± 1%
Frequency

50 Hz (60 Hz on request)

Frequency tolerance (line synchronized: ± 1%) (free running: ± 0.2%)
Efficiency at 100% load up to 93%
Crest factor 3 : 1
Overload protection (100%-125% load: 10min) (125%-150% load: 1min) (>150% load: by pass)
Short circuit protection electronic shor circuit protection
Total harmonic distortion <3%
BATTERIES
Typ Sealed Lead Acid - Maintenance Free
Number of batteries 20 30  
Float charging voltage   405 VDC  
End of discharge voltage 200 VDC 300 VDC  
Ambient temperature °C  25 °C
Battery protection Automatic circuit breaker
Battery test automatic and manual on request
GENERAL
Kommunikation Dry contacts & RS232; RS 485
Software T-Mon UPS Management Software
Temperature range  0°C - 40°C
Ventilation Forced air cooling
Relative humidity <90% non condensing
Protection degree IP 20
Altitude < 1000m above sea level
Accoustic noise < 50dBA < 55dBa
Weight w/o batteries (kg) 106 110 125 190 200 230
Dimensions HxWxD (mm) 950x265x740 1250x505x650
OPTIONS
Input transformer Galavanic isolation transformer at the input
Input THD not available < 10% with 18 pulse rectifier; < 5% with 18 pulse rectifier + filter
Parallel operation N +1 systems (hot standby, redundant, symetric parallel